CHAPTER 4
Refrigerants
Heat cannot be transferred from the inside of the refrigerator to the outside without some sort of medium or heat-carrying device. This medium is called refrigerant.
2. Just what is refrigerant? Well, the dictionary defines it as follows, “A substance, such as ice, liquid air, ammonia, or carbon dioxide, used in refrigeration.” We could define refrigerant as the medium (fluid or gas) used to transfer heat from the evaporator to the condenser.
3. The requirements for a refrigerant are almost self-explanatory. It is obvious that an automatic mechanism should be safe; that is, free from the danger of poisonous, flammable, or explosive gases. Refrigerants must be noncorrosive in order that the more common metal can be used in the construction of the machine part. It must also be such that its presence can be easily detected and traced to its source in the event of leaks. It is also desirable to keep pressures within the refrigeration cycle as close to atmospheric pressure as possible, for any great differences in pressures tend to cause leaks, overwork the compressor, and lower the overall efficiency of the system. Another desirable characteristic of a refrigerant is stability. If a refrigerant is to have this, then it must remain chemically unchanged while constantly going from a low temperature to a high temperature and back to a low temperature. It must not set up a chemical reaction with the lubricants used in the system. It must not chemically deteriorate if it comes in contact with air or moisture within the system.
4. There are various types of refrigerants used today. The choice depends upon the application. Each manufacturer attaches to his unit a nameplate which gives the type and amount of charge in the system. Changing to a different refrigerant should not even be considered, since most units are deigned for use with one specific refrigerant. Each refrigerant has a different pressure-temperature relationship. This relationship will be the topic of our next discussion.
18. Effect of Temperature and Pressure
18-1. As you learned earlier, we can liquefy any gas by lowering its temperature. At some temperatures the gas can be liquefied by increasing the pressure. However, there are temperatures at which gases cannot be liquefied regardless of the applied pressure. These are called critical temperatures.
18-2. For example, we can change steam to water by lowering its temperature below 212° F. or raising the pressure; but at 689° F. no amount of pressure will effect the change. Anyone living at a high altitude has noticed that boiled food must be cooked for a longer period of time or under pressure. Boiling temperatures of points are lower at lower atmospheric pressures and higher at higher atmospheric pressures. The critical pressure of a gas (water vapor) is the minimum pressure required to liquefy (condense) it at its critical temperature.
18-3. The critical pressure of a refrigerant must be above any condensing pressure that might be encountered during a cycle of operation; otherwise the high-pressure gas would not condense and the refrigeration machine would cease functioning. If the ordinary condensing pressures are up near the critical pressure, the amount of power required to compress the refrigerant is excessive; therefore the critical pressure of a refrigerant must be well above the normal condensing pressure.
18-4. If the critical temperature of a refrigerant is not higher than the condensing temperature, the hot gas coming from the compressor will not condense regardless of pressure. If the temperature differential is small, power consumption is excessive.
18-5. If the hot gas coming from the compressor doesn't cool, the refrigeration cycle is not complete. The heat transferred to the refrigerant in the evaporator cannot be dissipated at the condenser. What heat was transferred in the evaporator? The heat from the food and inclosed area.
This caused the refrigerant to evaporate. Let's explain this heat and vaporization process thoroughly.
18-6. Latent Heat of Vaporization. With the exception of the comparatively small amount of heat absorbed by vapor superheated in the evaporator and in that part of the suction line within the refrigerator space, all of the heat-absorbing or refrigerating capacity that a refrigerant has comes from its latent heat of vaporization. In other words it depends on how much heat the refrigerant requires per pound to be changed from a liquid to a gas. Everything else being equal, the refrigerant having the highest latent heat of vaporization is the most desirable.
18-7. Boiling Point and Condensing Temperature. Each refrigerant is made up of a combination of chemical elements. The various components of each differ in reaching their boiling point or the temperature at which they condense. The boiling point of a refrigerant is that temperature and pressure at which it is changed from a low-pressure liquid to a low-pressure gas. The heat required comes from the area to be lowered in temperature. The evaporator is the heat-absorbing section of a system. As stated before, the refrigerant R-12 has a boiling point of -21.7° F. at atmospheric pressure. This boiling point is well below the lowest evaporating temperature at which the system operates.
18-8. The critical temperature of a refrigerant is usually considerably higher than the condensing temperature and pressure required in an operational system. The critical temperature of R-12 is 233° F., and the critical pressure s 582 pounds pr square inch. The pressure temperature table for R-12, found in the appendix of this volume, will show the normal operating pressure corresponding to a given temperature. (Table 2)
18-9. The cooling medium, such as air or water, is cooler than the refrigerant as it enters the condenser. Heat is absorbed by the cooling medium and dissipated into the atmosphere which changes the state of the refrigerant from a gas to a liquid.
18-10. Classification of Refrigerants. Today there are a number of different refrigerants used by manufacturers of refrigeration machines. The following paragraphs are devoted to a discussion of a few different refrigerants, their characteristics, and the methods used in testing for leaks.
18-11. Ammonia (NH3). This refrigerant is used most in certain applications in industry and also in the absorption type refrigerator. Ammonia is colorless and has a pungent odor. It boils at -28°F. atmospheric pressure. When one volume of ammonia and two volumes of air are mixed, there is danger of explosion. Ammonia very toxic and requires heavy fittings. Units using ammonia must be water cooled. To detect ammonia leaks, the repairman uses a sulphur candle, the flame of which gives off a white smoke when it comes in contact with an ammonia vapor. Still another means of detecting an ammonia leak is the phenolphtalein paper method. A mild concentration of ammonia causes the paper to turn pink; heavier concentrations turn the paper scarlet. (Table 1)
8-12. Refrigerant (R-12). Refrigerant-12 is colorless and odorless both as a liquid and as a gas. If a heavy concentration of this gas is present, a very slight odor is evident, but the vapor will not irritate the skin, eyes, nose, or throat. R-12 boils at ‑21.7° under atmospheric pressure. The presence of moisture in R-12 does not cause corrosion; only a mild discoloration of brass, copper and steel results. It is noncombustible and also mixes readily with oil. To detect R-12 and other halogen refrigerant leaks the halide detector (as shown in fig. 69) may be used. Other methods may also be used.
Figure 69. Halide leak detector.
18-13. Carbon dioxide. Carbon dioxide gas is harmless to breathe except, of course, in heavy concentrations when all the oxygen is excluded. In such cases, suffocation results. It has a slightly pungent odor and an acid taste.
18-14. Because of its low efficiency as compared to others, this refrigerant is seldom used in household refrigerators. It is used principally in industrial systems and on ships.
18-15. Other refrigerants. Other refrigerants used to a great extent in the refrigeration industry try are Refrigerant-11, Refrigerant-22, and Refrigerant-11. Less commonly used refrigerants are Refrigerant-21, Refrigerant-113, butane, ethane, propane, and methyl formate. (Tables 3-5)
18-16. You must become familiar with the safety precautions related to refrigerants, for as we've mentioned previously, working safely benefits both the equipment and you.
18-17. Transfer of Refrigerants. Refrigerants are obtainable in amounts from railroad carload to a 1-pound can. However, most of the refrigerant is in 145-pound cylinders. These cylinders are too heavy for the serviceman to move from place to place so the refrigerant must be transferred into smaller containers. This is done by obtaining a small cylinder designed for the particular gas which is to be transferred. Connect a charging line, weigh the empty cylinder and cool it if possible (set in ice or other methods), invert the full cylinder, and open both cylinder valves. Stop the transfer when the small cylinder becomes 80-85 percent liquid full. CAUTION: Never fill a cylinder over 85 percent liquid full and always wear protective equipment when transferring refrigerant.
18-18. Let’s look at some of the “do's” and “don'ts” while handling refrigerant cylinders.
(1) Never drop cylinders or permit them to strike each other violently.
(2) Never use a lifting magnet or a sling when handling cylinders. A crane may be used when a safe cradle or platform provided to hold the cylinders.
(3) Cylinder valve caps should be kept on at all times except when the cylinders are in use.
(4) Never fill a refrigerant cylinder completely full of refrigerant. The safe limit is 85 percent full. Overfilled cylinders are apt to burst from hydrostatic pressure.
(5) Never mix gases in a cylinder.
(6) Cylinders are made to hold gas - don't use them for a support or roller.
(7) Never tamper with the safety device on a cylinder.
(8) Open cylinder valves slowly and use a cylinder valve wrench. Never use a monkey or Stillson wrench for this purpose.
(9) Never force misfitting connections; make sure that the threads of regulators and unions are the same as those on the cylinder outlet.
(10) Never attempt to repair or alter a cylinder or valves.
(11) Never store cylinders near flammables.
(12) Always keep cylinders in a cool place away from direct sun rays if possible and fully secured in place.
(13) Do not store full and empty refrigerant cylinders together. They should be stored in different sections of the shop to avoid confusion.
(14) Always insure that gas cylinders are secured in place both when empty and filled.
18-19. As we stated before, you should always wear protective equipment while charging or transferring refrigerant. However, if something happens when you do not have the protective equipment on and the refrigerant comes in contact with your eyes or skin, you should know the first aid that will help you. If the refrigerant comes in contact with the eyes they can be bathed in a 2-percent boric acid solution. For frostbite on the skin the area can be bathed with cold water and massaged around the area until circulation is restored. Do not disturb the frost blisters.
18-20. A refrigerant is the carrier of heat in a system; consequently, it is found in different parts of the system in different states. How do we know which state the refrigerant i in within the system? Very easy; we use the refrigerant table. Using the table, we can check the pressures within the system and convert the pressures to temperatures. This can also tell us if the system is safe to open. Remember, even though you know a little first aid, it's better to be safe than sorry.
18-21. Tables have been compiled through experiment and research for each of the most commonly used refrigerants. These tables show the pressure, density, volume, heat content, and latent heat corresponding to certain temperatures. The charts are so designed that when you have one condition given you can determine the other relative factors. (Tables 1-6)
18-22. We have had a discussion on a few of the most important refrigerants and their purpose as heat carriers in a refrigeration system. A refrigerant is the bloodstream of any refrigerator; it removes heat at a low pressure as it evaporates, and gives up heat at a high pressure as it condenses. The properties of a few of the most common refrigerant gases are discussed and the characteristics noted, as well as the safety precautions which are essential and must be observed. You are the one who will be handling refrigerant, so don't be careless, for they can cause personal injury. The sections covering safety precautions, safe handling of gases, and first aid treatment list the “dos” and “don'ts” to be followed when dealing with refrigerants. Read and heed; these are for your own benefit. Tables which will be used in every step of this course are contained in the appendix to this memorandum.