CHAPTER 4
Special Application Systems
SOMETIMES we try to make things more complicated than they are. You can avoid confining yourself if you keep in mind that a basic system is modified to make it work for a special application. Yet, not one of the systems basic principles is changed. This chapter deals with multiple evaporators and multiple compressors and concludes with systems for producing ultralow temperatures. Technical information on these systems is reproduced from Commercial and Industrial Refrigeration, by C. Wesley Nelson, copyright 1952, McGraw-Hill Book Company; used by permission. You are already familiar with the name of items which will be discussed, but differences result from the conditions under which this equipment operates. Let us consider first the problems of a system using several evaporators.
21. Multiple Evaporator Systems
21-1. A multiple system is one in which several evaporators are operated from one compressor. A variation is the operation of two or more compressors with one evaporator. Multiple units are installed in restaurants, soda fountains, bars, and in other places where more than one refrigeration fixture is used. Capacity control is obtained by using two or more compressors for one evaporator. An example is an ice plant when the compressors are started or stopped according to the load demand.
21-2. Classification of Multiple Evaporator Systems. Fundamentally there are only two classifications of multiple-unit systems. The first is the one in which all the evaporators operate at the same temperature. This is the simplest, although not the most common. The second is the one in which the temperatures in the different refrigerators are not the same. In order to control the temperature in a multitemperature installation, various combinations of valves and controls must be used. The correct selection and installation of these valves and controls have a decided bearing on the success of the installation.
21-3. Cord Valves for Multiple Units. When two or more evaporators are operated from the same compressor and the temperature of the warmer refrigerator is not more than 5° F. higher than the colder, no special valves are necessary. When the temperature difference is greater than 5° F., some sort of valve or control for the warmer refrigerator is essential. A thorough knowledge of the operation and application of the types of available control valves is necessary before a satisfactory multiple system can be laid out.
21-4. Suction-pressure regulating valve. This valve, also called an evaporator-regulating valve, is placed in the suction line of the warmer evaporator, and controls its pressure (and consequently its saturation temperature) so that it will remain substantially constant and not go below the predetermined setting of the valve. Thus, when two or more evaporators are operated with one compressor, the desired temperature in the warmer evaporators can be maintained by the proper setting of the valve. The locations of the valves in a system are shown in figure 39. (See paragraph 21-19.)
21-5. Bellows type. A bellows type evaporator-regulating valve has the inlet connection from the evaporator and the outlet connection to the compressor. The evaporator pressure acting under the bellows and the force of a small spring under the valve are both opposed by a spring. When the forces are equal, the valve is in equilibrium and maintains a definite opening. A reduction in evaporator pressure will cause an unbalancing of forces, and the valve will throttle. The resulting decrease in the flow of vapor will prevent the pressure from going too low. The condensing unit continues to operate on the other evaporators at reduced suction pressure. This valve has a fitting where the evaporator pressure may be taken. A gauge adapter valve must be used. The cap is removed and the adapter is screwed onto the fitting with the key engaging the needle valve. The gauge is connected to the adapter and, when the valve is opened, the pressure may be read. This fitting is also used in pumping down the evaporator. The regulating valve must be bypassed when pumping down, because it would close on reduction of suction pressure. To bypass the valve, a line is run from the adapter to the compressors suction-valve gauge port. If the distance is too great, a connection should be provided on the compressor side of the valve, as shown in figure 34.
Figure 34. Method of bypassing evaporator-regulating valve.
21-6. Diaphragm type. Another type of evaporator-regulating valve is illustrated in figure 35. This valve has a diaphragm instead of a bellows. One of the features of this valve is the collar with pressure graduations under the adjusting knob. By turning the knob until the bottom lines up with the graduations, you can make the correct setting without reading the pressure or without waiting for the refrigerator to arrive at the desired temperature. The operation of this valve is similar to the one previously described in that the valve remains open when the warmer evaporator pressure is high and then throttles as the compressor lowers the pressure. This valve has a gauge port for checking pressure and for bypassing. To get a reading, you attach the gauge to the port, remove the cap, and open the gauge shutoff valve. The valve range is from 40 p.s.i. to 0 in. Hg vacuum, and it can be used on Freon units up to 1/2 ton and up to 3/4 ton on methyl chloride and SO2 units.
(Courtesy Controls Company of America)
Figure 35. Diaphragm type evaporator-regulating valve.
21-7. Two-temperature type with manual closing. Still another type of two-temperature valve is the one shown in figure 36. You adjust this valve by the adjusting nut; the handwheel is used only for closing the valve without affecting the setting. You use the auxiliary valve when attaching a gauge. You may also use it to bypass the main valve when you want to pump out the coil. During normal operation, the auxiliary valve is closed, and when the coils being evacuated, the valve is turned into midposition. The valves mentioned above should be installed in a location where frosting will not occur and should be reasonably close to the refrigerator which is to be controlled. These valves may be used on flooded or direct-expansion evaporators, providing defrosting is not required.
Figure 36. Two-temperature valve with manual closing arrangement.
21-8. Snap-action type. A suction-pressure regulating valve of the snap-action type is not a throttling type and can be set to cut in and out at definite predetermined pressures. This valve is either wide open or closed tightly. You use it when you want to operate an evaporator on a defrosting cycle, and when a shorter operating time than that provided by the condensing unit is required. The effect of using a snap-action valve on an evaporator in a multiple system is the same as if it were connected to a separate compressor. This valve should be used only with a low-side float or with a thermostatic expansion valve. Most valves of this type have a gauge port to which a gauge may be attached to aid the proper setting.
21-9. Thermostatic type. A thermostatically controlled suction-pressure valve is shown in figure 37. This valve is used where close, nonelectrical control of single evaporators is desired. Such applications are sweetwater baths, water coolers, beverage coolers, and soda fountains. In multiple installations, you place the valves in the suction line from the warmer evaporator, with the thermal bulb in the refrigerated space or liquid. This valve gives closer temperature control than does the pressure type. The valve illustrated in the figure is of the snap-action type, but the thermostatic type is also available in a valve which has throttling action. Before the refrigerator has reached the desired temperature, the valve is wide open and the coil is subject to refrigeration from the condensing unit. When the desired temperature is reached, the valve snaps shut and the coil is isolated from the rest of the system. If the refrigerator temperature is above freezing, the coil will defrost while the valve is closed. You must install this valve in a horizontal part of the suction line, and place a strainer ahead of it. The bulb should be located where it will reflect the average conditions, and in water baths it should be placed in the liquid but not too close to the coils.
Figure 37. Thermostatically controlled suction-pressure valve.
21-10. Check valves. When evaporators are connected in multiple and the temperatures are different, the pressure in the warmer evaporator is higher than that in the colder. When the control valve opens, the high-pressure vapor in the warmer evaporator would back up into the colder evaporator if no means were provided to prevent it. This vapor would cause a warming up of the colder evaporator and would impair its efficiency. To prevent this, you install a check valve which will permit the vapor to flow in only one direction. See figure 39 for the proper location of check valves in a multiple system. Next, let us review some important points before discussing the use of solenoid valves in a multiple system.
21-11. Important Points for Multiple Installations. Because of the large number of possible multiple combinations, it is impossible to give a set of rules and expect them to apply to all cases. Although there are exceptions to the rules, the eight rules explained next should be adhered to whenever applicable.
(1) The coldest evaporator or evaporators must comprise more than one-half of the total load on the condensing unit. If the warmer evaporator were the major part of the load, the condensing unit would be operating at the higher suction pressure a greater portion of the running time and would not be able to bring the colder refrigerator down to the desired temperature.
(2) The capacity of the condensing unit is selected at the suction temperature or pressure of the colder evaporator. Since the colder evaporator constitutes the major part of the load, the compressor will be operating at its pressure most of the time, although the pressure in the warmer refrigerator will be higher. This is another case where we must remember that the capacity of a compressor is less at lower suction pressures.
(3) The evaporator for each refrigerator is selected at the suction pressure which will give the correct temperature and humidity for the particular application. The selection is made just as if each evaporator were to be connected to its own compressor.
(4) When the temperature difference between the colder and the warmer fixture is greater than 5° F., a control for the warmer evaporator or evaporators is necessary. This control may be either a suction valve of the pressure or temperature type or a solenoid valve. In some cases, although the temperatures are the same, one refrigerator will be used much more than the other. In instances like this, a control valve should be used and placed in the suction line of the refrigerator with the least usage.
(5) A snap-action type of suction-pressure control should be used if defrosting on the off cycle is required. This cannot be done, even though a snap-action valve is used, unless the refrigerator temperature is above 35° F.
(6) The coldest evaporator should always be directly connected to the compressor, and a check valve should be located in the suction line between the outlet and the first takeoff. In following the rule that half of the total load should be the cold evaporator, there is sufficient load on the compressor to eliminate low back pressure even though the control devices have isolated all the warmer evaporators.
(7) In general, thermostatic expansion valves should be used as the liquid control when direct expansion evaporators are installed in multiple. The control of temperature in any refrigerator should not be by the adjustment of any expansion valve. This should be done by the adjustment of the suction-pressure valve in order to obtain the best operating conditions.
(8) The liquid and suction lines should be sized according to the amount of refrigerant flowing and according to the load on each branch or main. These important points place a limitation on the applications in which a multiple installation should be made. When the temperature difference between the warmer and the colder refrigerators is greater than 25° F., multiplexing should be considered the exception rather than the rule unless humidity is not a factor. When high humidities are to be maintained, such as in florist's boxes, it is better to use a compressor for each evaporator.
21-12. Evaporators with forced convection. Although multiple installations can be made with all expansion coils, all low-side float coils, or with a combination of both, you must give extra thought when you want to use forced-convection coolers. A forced-convection unit must be caused to defrost during the OFF cycle unless some means for artificial defrosting is provided. In some multiple installations where the forced-convection unit is the colder evaporator, a sufficiently low suction pressure may occur so that the unit cannot defrost, and it thus become inoperative in a short time. If the forced-convection unit is the colder evaporator, successful multiplexing may be done if suction-control valves are used.
21-13. Low-pressure cutout. Multiple installations, where suction-pressure or temperature-control valves are used, have the colder refrigerator controlled by the low-pressure cutout at the condensing unit. The warmer refrigerator, in this type of arrangement, does not require any electrical control. The low-pressure electrical control is set at the proper cut-in and cut-out points just as if it were operating on a single evaporator. Some of the modern suction-control valves that are used on the warmer evaporators are calibrated so that the temperature setting can be made in advance. If this is not so, you must operate the system until the refrigerators come down to the desired temperature; you then adjust the control to shut off the evaporator from the compressor at this point. In any event, the final adjustment of the controls is governed by the thermometer readings in the various refrigerators.
21-14. Solenoid Valves in Multiple Systems. Solenoid valves are used extensively in a multiple system. They may be placed in either the liquid line or the suction line. Figure 38 shows a multiple hookup using solenoid valves in the liquid line. As may be seen from the diagram, there is a thermostat in each refrigerator, and each thermostat is connected to the solenoid valve that is in the liquid line leading to its refrigerator. The operation of the system is as follows: Assume that all the thermostats call for cooling and that the compressor is operating on all of the evaporators. When one thermostat is satisfied, it opens the circuit and the solenoid valve closes the liquid line to the evaporator. The compressor pumps out the refrigerant from that evaporator and continues t operate on the others. As each thermostat is satisfied, its solenoid valve closes; and finally, when all valves are closed, the compressor is stopped by a low-pressure cut-out.
Figure 38. Multiple system using solenoid valves.
21-15. There are several important factors that must be considered in connection with multiple systems using solenoid valves. As each solenoid valve closes, its evaporator is pumped out and the refrigerant is returned to the receiver. The receiver, therefore, must be large enough to hold the entire charge in the system. When the compressor is operating on all the evaporators, it is at full load and the suction pressure is high. As one evaporator after the other stops refrigerating, the suction pressure drops progressively lower. This drop in suction pressure has the disadvantage of continually upsetting the balance between the refrigerator temperature and the coil temperature. The result affects the humidity in the box and, in some cases, prevents the defrosting of the coil. A suction-pressure regulating valve placed in the suction line near the compressor will hold the pressure at the desired point in the evaporation although the crankcase pressure will be low when only one evaporator is operating from the compressor. The low-pressure control, which shuts off the compressor after the last solenoid valve closes, must be set lower than the suction pressure when the compressor is operating on only one evaporator. The setting of the cut-in point should be made so that the opening of one solenoid valve will start the compressor.
21-16. Solenoid valves that are used in the suction line from the evaporator should be selected so that the pressure drop through the valve will not be over 2 p.s.i. When a solenoid valve is so used, the refrigerant remains in the coil and does not return to the receiver. If the valve is placed in the suction line, there is danger of accumulated liquid flooding over into the compressor in the event of a leaking float or expansion valve.
21-17. Installation. A multiple system is installed like a simple one insofar as the coils and condensing units are concerned. In order to simplify service operations, a manifold is usually placed on the wall near the condensing unit. Three-way valves are sometimes used to allow the refrigerant to pass through the valve unobstructed on the run of the valve, while the branch line from the side outlet may be shut off. Prefabricated manifolds may also be obtained.
21-18. Evaporators at same temperature. When the temperatures are the same in all of the refrigerators, there is an expansion valve on each coil. When two coils are located in the same case, it is not good policy to connect coils in series, because the second coil will not maintain its rating. Two coils should not be connected to one expansion valve, regardless of whether they are in series or parallel. There are no pressure-control valves needed when all evaporators are operated at the same temperature. The entire low side of the system is controlled by a low-pressure control located on the base of the compressor unit.
21-19. Evaporators at different temperatures. The line diagram in figure 39 shows the connections for three coils at different temperatures. Note the presence of a suction-pressure control valve in each of the warmer coils. The suction line from the coldest evaporator is directly connected to the compressor with a check valve in the line. In this diagram, the -10° evaporator should constitute the major portion of the load. A check valve is also found in the suction line from the 35° evaporator, since this evaporator is colder than 45° and there would be the possibility of the warm vapor backing up and condensing,
Figure 39. Multiple systems using evaporative-regulating valves.
22. Multiple Compressors
22-1. Compressor units are sometimes connected in parallel to obtain greater flexibility or to use small units on one evaporator where a larger one that will balance properly is not obtainable. The practice of operating compressors in multiple is not new; in fact, it is quite common in ammonia plants and cold storage warehouses. The principle difficulty in interconnecting condensing units is in the oil return to the crankcase. Ammonia does not present any problem in this regard, since oil and ammonia are not miscible. Freon, methyl chloride, and other oil-miscible refrigerants, on the other hand, present a real difficulty when condensing units that use them are interconnected. Multiple installations of condensing units should be avoided and made only when it is not possible to split up the units that each evaporator has its own condensing unit.
22-2. Connections Between Compressors. Compressors that are to be interconnected should be of the same manufacture and preferably of the same size. A good installation is one in which each condensing unit will carry its share of the load and the oil return will be such that the proper level will be maintained. To get this balance of the load, the liquid, suction, and discharge lines are interconnected and it is necessary that oil- and gas-equalizer lines are installed between the crankcases. The compressors should be placed close to each other so that the connecting lines will be as short as possible.
22-3. Balanced refrigerant lines. Lines should be connected as shown in figure 40 so that the elbows and length of pipe from the tee to one compressor are the same as to the other compressor. Thus the frictional resistance between each receiver and the manifold should also be approximately the same. Both suction and discharge lines should be balanced in the same manner as we have just described. Suction lines should be connected so that the oil which is returning through the line will divide between the compressors as evenly as possibly. Suction lines from a manifold to the compressor, if used, should be taken off at the side to facilitate oil return.
Figure 40. Balanced lines between compressors.
22-4. Oil-equalizer line. The crankcase oil-equalizer line may be connected in one of two ways, A or B, a shown in figure 41. The A method is preferable although the B method is more often used because of the location of plugs in the crankcases of some compressors where the equalizer lines may be connected. In the method shown in A, the oil-equalizer connection should be made at the lowest safe oil level. Condensing units should be placed on their foundations so that the oil level in each is in the same horizontal plane. The gas-equalizer connection is made above the maximum oil level. All equalizer lines should be level. The size of the manifold to which the various branches are connected should be at least equal in area to the sum of the branches. Crankcase oil- and gas-equalizer lines should be not less than 3/4-inch ID up to 10 tons capacity and l-inch ID over 10 tons.
Figure 41. Oil equalizer lines.
22-5. Control of Multiple Compressors. When condensing units are interconnected for purposes of capacity control, usually you have to provide a means for starting and stopping the compressor according to load demands. The compressors are manually operated only when an operator is in attendance and when load changes can be anticipated beforehand. For liquid or air cooling, if close temperature control is not required, two temperature controls may be used, one being set a degree or two higher than the other. A more common method is to use pressure controls on the common suction line, set in sequence so that the compressors will start and stop according to changes in suction pressure. When this method is used, thermostats and solenoid valves are almost always installed.
22-6. When a number of compressors are connected together or when an installation consists of a number of single evaporator and condensing-unit installations in one refrigerated space, situations occur in which all compressors will start at the same time. This puts a very heavy load on the electric lines and power system. A timer, which will delay the starting of compressors until after the first one, should be installed. The action of the timer is such that when the contactor for the first compressor has closed, there is a delay of 10 or 15 seconds before the timer closes the control circuit of the second compressor and allows it to start. If there are more than two compressors, a timer may be used on each except the first one.
23. Ultralow Temperature Systems
23-1. The use of ultralow-temperature refrigeration in industrial work has increased tremendously in the past few years. Commercial units are now manufactured to produce temperatures below -100° F. for various applications. An example is the production testing of various instruments and appliances, such as radios, cameras, clocks, and meters which may be subject to low temperatures in arctic climates or in outer space. Ultralow temperatures find application in various kinds of metal treatment. The hardness of certain kinds of steels has been materially increased after a conventional hardening process by lowering the temperature to about -110° F., allowing them to warm to room temperature, and then tempering. Another development is the shrink-fitting of parts by using cold instead of heat. The male part is reduced in temperature to -100° F., after which it is fitted to the female part and the unit allowed to warm to room temperature. The extensive use of aluminum riveting in aircraft and other metal work has led to the use of special alloy rivets which may be prevented from age hardening and kept soft by holding them at -40° to -45° F. until ready for use.
23-2. Test chambers which are designed for simulating conditions encountered by military and other aircraft are being used increasingly. They are used for testing instruments, clothing, military weapons, and equipment that is normally carried in an airplane. Weather bureau information shows a temperature of -50° to -60° F. at elevations around 50,000 feet, and cabinets for testing are usually kept between -60° and -70° F. Some cabinets are equipped so that any temperature from +100° to -100° F. may be obtained.
23-3. Insulation Requirements. Ultralow-temperature cabinets require more consideration in regard to insulation and construction than do zero cabinets. Insulation thicknesses of 10 and 12 inches are needed, and extra care must be taken with vaporproofing to prevent the entrance of moisture. When a refrigerator is intended to maintain a low temperature at all times, it is usually desirable to use an insulating material which has a high thermal capacity such as cork. Any interruption in refrigeration will not be so serious because of the slow warming up of the box. On the other hand, when rapid fluctuations in temperatures are desired, such as in simulated flight, an insulation of low heat capacity should be used. Ferrotherm (a number of thin steel sheets with air spaces) and Santocel (silica aero-gel) are two such insulating materials. Tests at Wentworth Institute using dry ice in a box insulated with nine sheets of Ferrotherm with 36-inch air space between the sheets gave a temperature reduction from +70° to -70° F. in 45 minutes.
23-4. Refrigerant and Compressor Problems. A simple refrigeration cycle is neither suitable nor economical for ultralow-temperature application. In order to obtain heat extraction from a box at a temperature of, say, -70° F., it is quite evident that a coil temperature less than -70° F. is necessary. If a 10° F. temperature difference were assumed, a design temperature of -80° F. for the coil would be used. If Freon 12 were the refrigerant selected, the corresponding absolute pressure and volume would be 2.885 p.s.i.a. and 11.57 cubic feet respectively. This would give a compression ratio of over 30 to 1 with normal condensing temperatures. This is much higher than is possible with a conventional compressor. As a matter of fact, a compressor operating with any such ratio would not discharge vapor but would simply compress and expand the vapor in the cylinder without doing any useful work. The compression ratio for units working under average commercial conditions is approximately 4 to 1. Ratios up to 8 to 1 are considered as being satisfactory for a single compressor. When ratios are above these values, because of extremely low temperatures, you must employ staging in order that there will be less work required per ton of refrigeration.
23-5. Staging. In a simple compression system, the heat that is absorbed at the low level of temperature is rejected at a higher level in one step. In a low-temperature application where this is either impossible or impractical, the heat may be "pumped" in two or more steps. This is called staging. Staging may be done by two methods in refrigeration work: (1) by using compound compression in which the vapor is removed from the evaporator by the low-pressure compressor and discharged by it to the high-pressure compressor, which discharges to the condenser in the usual manner; (2) by using an arrangement called cascading which is, in effect, two cycles operating at different heat levels. The low-pressure compressor discharges into a condenser which is the evaporator for the high-pressure cycle. The final heat is rejected to the cooling water as in the simple system. In direct staging the same refrigerant is used throughout, while in the cascade system different refrigerants may be used in the high- and low-pressure stages.
23-6. Compound Systems. Although a compound compression system consists essentially of two or more compressors in series, the addition of intercoolers and subcoolers will increase the efficiency and reduce the cost of operation. Of the several arrangements, two of the most common, the direct compound and the cascade systems, are included here.
23-7. Direct compounding. Direct compounding with an intercooler is illustrated in figure 42. This is a two-stage compression in which the refrigerant vapor is drawn from the evaporator through the heat exchanger by the first-stage compressor. The discharge from this compressor passes through a water-cooled intercooler, which is located between stages, and from there to the suction of the high-pressure compressor (second stage). The vapor is then liquefied in the condenser and flows through the other side of the heat exchanger to the expansion valve. The use of an intercooler reduces the superheat and the work of compression. The piston displacement of the low-pressure compressor is greater than that of the high-pressure compressor because of the greater volume of the vapor at low pressure. The proper sizing of the high- and low-pressure cylinders is such that the desired capacity will be obtained, and the compression ratios for each compressor will be approximately the same and within reasonable limits. When two individual compressors are used, they should be at the same level, and oil-equalizer lines between them must be provided as shown in the illustration. The intermediate pressure which exists between stages is not controlled and will fluctuate within small limits as the load varies.
Figure 42. Direct compounding with an intercooler.
23-8. A compound compression system with a liquid subcooler is shown in figure 43. The colder the refrigerant when it enters the expansion valve, the less flash gas will be formed when the refrigerant cools down to the evaporator temperature. The purpose of the subcooler is to subcool the refrigerant and thus increase the refrigeration effect. Referring to the diagram, you see that the liquid leaves the condenser, and a potion of it expands in the subcooler coil at the suction pressure of the high-pressure compressor. The remainder, at a much lower temperature, leaves the subcooler and goes to the expansion valve. What actually happens here is that the flash gas generated in the coil of the subcooler need only be compressed in the high-pressure compressor. The vapor has a smaller volume at this intermediate pressure, and for these reasons, a considerable amount of work may be saved. Without the subcooler, the flash vapor would have to be compressed from the evaporator pressure, where the volume is high, through both the first- and second-stage compressors. This arrangement, or one which will attain similar results, is a necessity in ultralow-temperature refrigeration. In place of single compressors, a V-design of a compound compressor is used in smaller size units. This type of compressor requires only one motor and eliminates the problem of oil level equalizing.
Figure 43. Direct compounding with a subcooler.
23-9. Cascade systems. A cascade system consists of two or three separate simple cycles operating in conjunction with each other at different temperature levels. The connecting point is a heat exchanger between the stages. This interstage heat exchanger is the condenser for the first stage and the evaporator for the second stage. An elementary diagram of a cascade system is shown in figure 44. Beginning with the low-pressure cycle, the vapor from the evaporator is compressed in the first-stage compressor and goes to the interstage heat exchanger, where it gives up its heat to the second-stage evaporator coil. The condensed liquid then flows to the first-stage expansion valve and the evaporator, completing the low-pressure cycle. The vapor which is generated in the coil in the heat exchanger because of the heat it has absorbed is compressed in the second-stage compressor, and the high-pressure vapor is condensed, its heat going to the cooling water. Each stage is an independent simple cycle, and for this reason has some advantages over the compound compressors. There is no problem of oil equalizing, and a different refrigerant may be used in each stage. There is some loss in the cascade system because a temperature difference must exist in the heat exchanger in order that the heat from the first stage will flow into the second stage. At the present time, the use of Freon 22 in the low stage and Freon 12 in the high stage will produce temperatures down to -90° F.
Figure 44. Elementary cascade system.
23-10. A two-stage cascade system with a second heat exchanger for subcooling the liquid and with an oil separator in the discharge of the first stage compressor is show in figure 45. There are a number of variations of this arrangement as far as the location of the second heat exchanger is concerned. The interstage heat exchanger, however, is always located in the same place- between the two stages.
(Copyright 1952. McGraw-Hill Book Company. used by permission.)
Figure 45. Two-stage cascade system.
23-11. Refrigerants for Compound Systems. At the present time, the number of refrigerants that are suitable for ultralow-temperature applications are few. Of the common refrigerants, ammonia SO2, methyl chloride, and CO2 are not used. Ammonia and methyl chloride have higher specific volumes than either Freon 12 or Freon 22, and SO2 has a freezing point of -98° F., in addition to a high boiling point. Carbon dioxide becomes a solid when it expands to a temperature below -70° F. Freon 12 and especially Freon 22 possess the best characteristics for low-temperature applications. The condensing pressure of Freon 12 at 80° F. is 98.76 p.s.i.a., whereas for Freon 22 it is 159.7 p.s.i.a. Compressors designed for Freon 12 may ordinarily be used with Freon 22, but in the large sizes particularly, compressors designed for Freon 22 should be used. The displacement of the compressor is les for Freon 22 than it is for Freon 12. Therefore a Freon 12 compressor would have a greater capacity when using Freon 22 than when using Freon 12. Under some conditions, then, a larger motor would be required when using Freon 22. In systems under 10 h.p., other parts such as liquid and suction lines would be the same as for Freon 12. Ethane, ethylene, and methane are hydrocarbon refrigerants which are occasionally used in applications where the temperatures are below -100° F. These refrigerants are explosive and are, therefore, unacceptable where there would be a hazard. Freon 13 is a refrigerant which is replacing the hydrocarbons for ultralow temperatures. All of the low-boiling-point refrigerant have high head pressures, and pressure-relief valves must be provide wherever they are used.
23-12. Controls. In an ultralow-temperature system, the flow of refrigerant to the evaporator may be controlled either by an expansion valve or by a float control. Ordinary expansion valves are not suitable because excessive superheating at the bulb location is necessary to operate the valve. A differential-temperature expansion valve designed for ultralow application has two power element operated by thermal bulbs. When an expansion valve is used, a solenoid valve is always placed ahead of it, and the coil is pumped down at the end of the running cycle.
23-13. The high-side float is used quite extensively and is simple and inexpensive. When used with an accumulator, the charge is not too critical, and since the float valve is in the high side of the system, any moisture is less subject to freezing.
23-14. There are various ways to wire the controls in a compound compression system, depending on the particular application. In a system which consists of one condensing unit and one evaporator, the simplest arrangement is to use a solenoid valve and a low-pressure cutout with a temperature control in the refrigerated space. The temperature control actuates the solenoid valve, and the pressure control operates the compressor. A special cutout must be used since the conventional tools are not satisfactory for vacuums over 20 inches Hg. Design of these control circuits should consider overload protection because of heavy loads and excessive pressures which occur during pulldown. The electrical controls for cascade systems consist fundamentally of a set of controls for each cycle.
23-15. Lubricating Oil for Low Temperature. It is very important that the lubricating oil which is to be used for low-temperature applications be an oil from which no wax will separate at or below the lowest expected operating temperature. The Freons as well as other chlorinated refrigerants possess solvent-extraction properties which remove wax from oil. With a refrigerant-oil mixture, there are two conditions which bring about wax separation. These are low temperatures and a high percentage of oil in the mixture. The use of a high-grade oil which has been processed especially for low-temperature refrigeration and the use of oil separators will minimize if not eliminate wax formation.
23-16. An expansion valve or other refrigerant control in which there has been wax formation acts somewhat like one in which moisture has frozen. With wax formation, the valve will "let go" at a temperature lower than 32° F. if heated. Also, if the valve is taken apart, the wax may be seen in the orifice or at the outlet. Such conditions would indicate that a poor grade of oil had been used in the system.
Practice Exercise